HomeGuides › Temperature
Selection guide · Temperature

How to Select an RTD Sensor — Pt100 Specification Made Simple

A Pt100 is a simple device with eight decisions attached to it. Get these right and the sensor will outlast the plant it is in.

Short answer

Element
Pt100 Class A for process, Class B where cost matters, 1/3 DIN for precision.
Wires
Three wire for almost everything. Four wire for laboratory accuracy. Never two wire on a long run.
Sheath
SS316 as standard, Inconel 600 above 600 °C.
Insertion length
Enough that the tip sits in the flowing stream, not in the boundary layer.
Head
Weatherproof die-cast for outdoors; Ex d if the area is classified.

At a glance

ChoiceOptionsRule of thumb
ElementPt100, Pt500, Pt1000Pt100 unless a long cable or a specific instrument demands otherwise
Accuracy classClass B, Class A, 1/3 DIN, 1/10 DINClass A for process control; higher classes cost and drift-check more often
Wiring2, 3 or 4 wire3 wire cancels cable resistance and covers 95% of duties
Simplex / duplexOne or two elementsDuplex gives a spare or a second loop with no extra pocket
Sheath materialSS316, SS310, Inconel 600SS316 to 600 °C, Inconel above
Sheath diameter3, 4.5, 6, 8 mmThinner responds faster; thicker survives longer
Insertion lengthMade to orderTip should reach the middle third of the pipe
HeadWeatherproof, Ex d, DIN BEx d only if the area classification requires it

Step by step

1
Fix the accuracy class before anything else

Class A Pt100 is specified to about ±0.15 °C at 0 °C, Class B to ±0.3 °C. A 1/3 DIN element is tighter still. Buying a tighter class than the loop can use is wasted money, because the transmitter and the wiring add their own error.

2
Use three wire unless you have a reason not to

Two wire adds the resistance of the cable straight into the reading — on a 50 metre run that can be a full degree. Three wire cancels it. Four wire is the laboratory answer and is only worth it when the whole loop is that accurate.

3
Choose the sheath for the temperature and the chemistry

SS316 to about 600 °C. Inconel 600 above that. In chloride service, SS316 pits — consider Inconel or a coating. The sheath is the part that fails first, so it deserves more thought than the element.

4
Set the insertion length from the pipe, not from the catalogue

The tip should sit in the moving stream, roughly the middle third of the pipe. Too short and it reads the pipe wall; too long and it can vibrate. Add the thermowell lagging extension if the line is insulated.

5
Ask for spring loading if it goes in a thermowell

A spring loaded assembly pushes the tip against the bottom of the well. Without it there is an air gap, and an air gap slows the reading by tens of seconds and biases it low.

6
Decide duplex now

A duplex element costs a little more and gives you a spare inside the same pocket. On a point that needs a shutdown to access, that is the cheapest insurance you can buy.

7
Choose the head by the environment, not the price

A weatherproof die-cast head with a proper double compression gland keeps water out. Water in the head is the single most common cause of drifting RTD readings in Indian plants.

8
Consider a head mounted transmitter

It converts to 4-20 mA at the sensor, so ordinary copper carries the signal and cable resistance stops mattering. It also lets you use a two wire loop instead of three or four cores.

Quick rules

For sanitary lines

Tri-clover RTD with polished wetted parts and no crevice — a threaded sensor is not acceptable in hygienic service.

For rotating machinery

Mineral insulated RTD, or a thermocouple. A conventional RTD element does not last under heavy vibration.

For hazardous areas

Flameproof Ex d head with a CCoE certificate, and an Ex d double compression gland on the cable entry.

Frequently asked questions

What is the difference between Class A and Class B Pt100?

Tolerance. Class A allows about ±0.15 °C at 0 °C, Class B about ±0.3 °C. The gap widens as temperature moves away from zero.

Is three wire or four wire better for a Pt100?

Four wire is more accurate because it cancels all lead resistance, but three wire cancels enough for process control and needs one core less. Use three wire unless the loop is a precision one.

How long should the insertion length be?

Enough that the sensing tip sits in the flowing stream — as a rule, the middle third of the pipe bore, plus the nozzle and any lagging extension.

What is spring loading and why does it matter?

A spring in the sensor assembly pushes the tip firmly against the bottom of the thermowell. Without it, an air gap forms, and the reading becomes slow and biased low.

Can a Pt100 be used above 600 °C?

With an Inconel sheath, up to about 650 °C in some designs, but the element drifts. Above that, use a thermocouple.

Still not sure? Talk to an engineer, not a salesman.

Send the process temperature, the pipe bore and the head you need. We will fix the class, the wiring, the sheath and the insertion length.